Harmonics, in an electrical power system, are currents and voltages with frequencies that are integer multiples of the fundamental power frequency. That is, in a power system with a fundamental frequency of 60 Hz., the second harmonic is 120 Hz., the third harmonic is 180 Hz., etc., etc.
Harmonic currents are created by non-linear loads that generate non- sinusoidal currents. Harmonic currents, acting in an Ohm's Law relationship with the source impedances, produce harmonic voltages.
The harmonic currents and voltages produced by balanced, three phase, non-linear loads are positive sequence harmonics (phasors displaced by 120 degrees, with the same rotation as the fundamental frequency), and negative sequence harmonics (phasors displaced by 120 degrees, with a reversed rotation).
However, harmonic currents and voltages produced by single phase, non- linear loads, which are connected phase to neutral in a three phase, four wire system, are third order, zero sequence harmonics (the third harmonic and its odd multiples - 3rd, 9th, 15th, 21st, etc., etc., phasors displaced by zero degrees). These third order, zero sequence harmonic currents, unlike positive and negative sequence harmonic currents, do not cancel but add up arithmetically at the neutral bus.
SOURCE OF THIRD ORDER, ZERO SEQUENCE HARMONICS
High levels of third order, zero sequence harmonics are principally the by- product of switchmode power supply technology which is used in modern office equipment and lighting systems, and in virtually all other low power electronic devices. These power supplies are efficient, small, light weight and low cost, and are in all other respects, highly suited to their task.
Electrically, the AC source voltage of these devices is rectified to DC voltage and then used to charge a large capacitor. In one half cycle the capacitor is charged to the average value of the voltage sine wave. The electronic equipment then draws current from the charged capacitor, to a regulated lower limit, to power the device's circuitry. Before reaching that lower limit, the capacitor is again recharged to the average value in the next half cycle of the sine wave. This process, which is repeated twice in each cycle, causes AC current to flow only during a portion of the AC voltage wave in abrupt pulses. During the rest of the wave, when the voltage is below the capacitor's residual, the capacitor draws no current.
Equipment containing switchmode power supplies includes personal computers, mainframe terminals, printers, photocopiers, facsimile machines and electronic ballasts in fluorescent lighting fixtures. On average, the zero sequence (180 Hz.) current generated by these devices exceeds 80% of the fundamental (60 Hz.) current consumed. For example, a personal computer, which consumes 1.08 Amperes fundamental current, was found to generate 0.90 Amperes third order, zero sequence current (83% of the fundamental).
In isolation, these rather small non-linear loads may seem insignificant. However, in the numbers found in today's modern offices and data centers, their impact may be costly and even dangerous.
EFFECT OF THIRD ORDER, ZERO SEQUENCE HARMONICS
Significant levels of third order, zero sequence harmonic current and voltage in a low voltage (i.e. 120/208V), three phase, four wire system will have a severe impact on both the power distribution system and the devices connected to it. In considering the extent of this power quality problem, it is important to understand that, unlike positive and negative sequence harmonics, zero sequence harmonics do not normally propagate into the higher voltage levels of the distribution system. They are contained within the low voltage distribution transformer and its secondary, four wire system.
Depending upon the capacity and configuration of the distribution system, the presence of third order, zero sequence currents may include any or all of the following symptoms:
Ironically, the devices which create the third order, zero sequence harmonics may be the most sensitive to the problems they create. The performance of the switchmode power supply, in particular the charging of its capacitor, is critically dependent on the magnitude of the peak voltage. These voltage harmonics can cause "flat topping" of the voltage waveform or lowering of the peak voltage. In severe cases the computer may reset due to its own power supply's failure.
THE SOLUTION - FINDING HARMONICS
There are a number of practical steps that can be taken to confirm the presence of harmonics in the electrical power system. (The inclusion of these procedures in a predictive/preventive maintenance program is fundamental to assuring power quality.)
Third order, zero sequence harmonic currents may also result in the
overloading of the transformers' neutral terminals. Neutral currents may
exceed phase currents under these harmonic conditions.
If "Average Responding" meters are also available, further proof may be obtained by repeating the above tests and comparing the results. If the current and voltage waveforms are sinusoidal, the results of both measurements will be the same.
Since "Average Responding" meters are only accurate under pure sine
wave conditions, any distortion of the waveform will cause the "Average
Responding" meter to read low. This reading may be as much as 50%
lower than the "True-RMS" reading. By dividing the results of the
"Average Reading" meter by the "True-RMS" meter, one may obtain an
"A/R" Ratio. A ratio of 1 would indicate little or no distortion while 0.5
would indicate substantial harmonic distortion.
MEASURING HARMONICS
In order to develop an engineered solution to this power quality problem, it is usually necessary to measure the harmonics using a harmonics analyzer. These measurements will provide detailed information on the full spectrum of harmonic currents and voltages, including:
AN ENGINEERED SOLUTION
Excessive third order, zero sequence harmonic currents, that occur in the neutrals of low voltage distribution systems in commercial buildings and data centers, first drew attention in the mid 1980s. Both the density of non-linear loads and the rapid increase of their use, previously unseen, introduced rather unique problems to which solutions did not really exist at the time.
Today, a number of solutions have been proposed to address this phenomenon. Whether applied at the design stage or later when a problem is discovered in an existing installation, the basis of these recommendations has been to derate or oversize certain system elements, particularly the power transformer and the neutral conductors. These suggestions, unfortunately, may introduce a whole new set of problems - an increased fault withstand requirement and short circuit interrupting level.
The most practical solution to this problem, however, is the removal of the zero sequence harmonic currents. One conventional solution is the application of an LC shunt filter tuned to the 3rd harmonic. This device, however, is case specific. If the harmonic current increases beyond the filter's design criteria, it will become overloaded. In this condition, capacitor fuses will interrupt and the filter's tuning will be shifted. In this condition the filter will not remove the desired harmonic current.
Harmonic Filters have been developed to directly *cancel* harmonics in a power system. The Filter has the characteristics of an ideal zig-zag auto transformer with high positive and negative sequence impedance, ultra low zero sequence impedance, high Q (quality factor), low losses, at the fundamental frequency and all appropriate lower order harmonics. A full line of CSA approved, UL listed Harmonic Filter is available from United Energy Associates, Inc.
As with any harmonic mitigation technique, a detailed system study may be required in order to predict a result. Moreover, the misapplication of any device, intended to correct this problem, can have serious system implications. United Energy Associates, Inc. offers ENGINEERED SOLUTIONS for the mitigation of all power system harmonics.
The Harmonic Filter solution has no parallel in the industry and advances the engineering of power distribution. United Energy Associates' Harmonic Filter directly corrects the harmonic distortion problem providing high quality power for modern electronic machines and is guaranteed to work. Harmonic Filter solutions available for office buildings are designed to fit the facility's power system.
THE BENEFITS:
Comparison of Alternative Methods for Resolving Harmonic Distortion
Feature K-Rated Derated Doubling Harmonic Transformer Transformer Neutrals Filter ________________________________________________________________________________ Shunts Zero Sequence Harmonics No No No Yes Reduces Neutral Current No No No Yes Safeguards Neutral Conductors No No No Yes Improves System Protection Slight Slight Maybe Yes Reduces Neutral to Ground Voltage No No Slight Yes Reduces Peak Phase Current No No No Yes Reduces Average Phase current No No No Yes Reduces Transformer Overload Yes Yes No Yes Increases System Capacity No No No Yes Reduces System Losses Slight Slight Slight Yes Reduces Total Harmonic Distortion No Slight Slight Yes Improves PF For Non-Linear Loads No No No Yes Improves Phase Current Balance No No No Yes Improves Phase Voltage Balance No No No Yes Carry Through Single Phase Outage No No No Yes Installs Without Shutdown No No No Yes Stand Alone Solution No No No Yes Harmonic Overload Capability Maybe Maybe Maybe Yes Cost Effective Solution No No No YesNote: Installing a Derated or K-Rated Transformer requires at least Doubling the Neutral Conductors.